1、发电厂接地系统设计规定一、GrO八ding SgSteM DeSig八接地系统设计The grounding and lightning protection system shall be designed per IEEE -80 and local codes and statutes, and shall consist of an integrated network of grounding conductors and ground rods. The final number of grounding rods and the actual quantity of ground
2、ing conductors shall be based upon the Job Site topography, an analysis of existing soil data, and the Contractor s soil resistivity testing. All grounding conductors utilized in the grounding system shall be barez hard-drawn copper throughout. All grounding rods shall be three (3) meters minimum le
3、ngth, copper-weld-type throughout. All grounding test wells shall be pre-cast concrete throughout with distinctive flush surface-mounted removable covers.接地与防雷保护系统应根据电气与电子工程师协会-80及地方规范和 法规行设计,并且应由接地导线和接地棒组成的综合接地网。接地棒的 最终数量和接地导线的实际数量应根据工程现场地势条件,现有土壤数 据分析,以及承包商土壤电阻率测试结果最终确定。接地系统中使用的 所有接地导线应采用硬铜裸导线。所有接
4、地棒的长度至少为三(3 )米, 并且应采用铜焊接地棒。所有接地测试并应采用预铸混凝土,并且配有 找平安装可移除井盖。The grounding system shall be designed to achieve the following:接地系统的设计应能够满足以下条件:1. Establish a minimum resistance to earth at all locations not to exceed one (1) ohm.各位置最小接地电阻不得超过一(1)欧姆。2. Protect personnel from dangerous potentials such as
5、transferred, step and touch potentials during both normal operating and maximum ground faults.保护人员免受危险影响,例如在正常操作或最大接地故障情况下发生传递电位、跨步电压或接触电压。3. Provide connection to ground for power equipment neutrals.为电力设备中性点提供接地。4. Facilitate relaying in clearing ground faults.促进接地故障保护继电器清除接地故障。5. Safely and effect
6、ively dissipate lightning charges.安全有效地使雷电电荷消散。All Facility electrical equipment, including both the above-grade and below-grade raceway systems, all motor frames, and all switchyard apparatus shall be tied to the grounding system and to each other. All Facility mechanical apparatus, including all o
7、utdoor and building steel support columns, platforms, stairways, elevated structures, and metallic tanks and vessels, shall be tied to the grounding system.所有设施电气设备,包括地上与地下电缆管道系统.所有电机座和所有 开关站装置,应与接地系统及彼此连接。所有设施机械设备,包括所有 室外和建筑钢制支撑柱.平台.楼梯、高架结构.金属罐和容器应与接 地系统连接。In both the GIS building and the outdoor F
8、acility switchyard areas, the grounding system shall be a subsurface rectangular grounding grid composed of overlapping 240mm2 minimum copper conductor, arrayed on a 4.57 meter x 4.57 meter maximum conductor spacing. This rectangular grounding grid shall extend under all transformer basinsfoundation